CHV100 Series Close Loop Vector Control Inverter
.69.
Function
Code
Name
Description
Setting
Range
Factory
Setting
function
terminal
P5.09
S6 Terminal
function
Programmable multifunction
terminal
0~55
0
P5.10
S7 Terminal
function
Programmable multifunction
terminal
0~55
0
P5.11
S8 Terminal
function
Programmable multifunction
terminal
0~55
0
Notice: P5.07 is only used when P5.00 is set to be 1 or 3. P5.08 is only used when
P5.00 is set to be 2 or 3.
The meaning of each setting is shown in following table.
Setting
value
Function
Description
0
Invalid
Please set unused terminals to be invalid to avoid
malfunction.
1
Forward
2
Reverse
Please refer to description of P5.13.
3
3-wire control Please refer to description of P5.13.
4
Jog forward
5
Jog reverse
Please refer to description of P8.06~P8.08.
6
Coast to stop
The inverter blocks the output immediately. The motor
coasts to stop by its mechanical inertia.
7
Reset fault
Resets faults that have occurred. It has the same function
as STOP/RST.
8
Pause running
When this terminal takes effect, inverter decelerates to
stop and save current status, such as PLC, traverse
frequency and PID. When this terminal takes no effect,
inverter restores the status before pause.
9
External fault
input
Stop the inverter and output a alarm when a fault occurs in
a peripheral device.
10
Up command
The reference frequency of inverter can be adjusted by UP
command and DOWN command.