CHV100 Series Close Loop Vector Control Inverter
.125.
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P4.00
V/F curve
selection
0:Linear curve
1: User-defined curve
2: Torque_stepdown
curve (1.3 order)
3: Torque_stepdown
curve (1.7 order)
4: Torque_stepdown
curve (2.0 order)
0
◎
V/F CURVE
P4.01
Torque boost
0.0%: auto
0.1
%
~10.0
%
1.0
%
○
TORQUE
BOOST
P4.02
Torque boost
cut-off
0.0%~50.0% (motor rated
frequency)
20.0%
◎
BOOST
CUT-OFF
P4.03
V/F frequency 1 0.00Hz~ P4.05
5.00Hz
◎
V/F FREQ 1
P4.04
V/F voltage 1
0.0%~100.0%
10.0%
◎
V/F
VOLTAGE 1
P4.05
V/F frequency 2 P4.03~ P4.07
30.00Hz
◎
V/F FREQ 2
P4.06
V/F voltage 2
0.0%~100.0%
60.0%
◎
V/F
VOLTAGE 2
P4.07
V/F frequency 3 P4.05~ P2.01
50.00Hz
◎
V/F FREQ 3
P4.08
V/F voltage 3
0.0%~100.0%
100.0%
◎
V/F
VOLTAGE 3
P4.09
V/F slip
compensation
0.00~10.00Hz
0.0Hz
○
V/F SLIP
COMP
P4.10
AVR function
0: Disabled
1: Enabled all the time
2: Disabled during
deceleration
1
○
AVR
P4.11
Auto energy
saving selection
0: Disabled
1: Enabled
0
○
ENERGY
SAVING
P4.12
FWD/REV enable
option when
power on
0: Disabled
1: Enabled
0
○
FWD/REV
ENABLE