CHV100 Series Close Loop Vector Control Inverter
.140.
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P8.29
Auxiliary motor
selection
0: Invalid
1: Motor 1 valid
2: Motor 2 valid
3: Both valid
0
◎
AUXILIARY
MOTOR
P8.30
Auxiliary motor1
START/STOP
delay time
0.0~3600.0s
5.0s
○
MOTOR 1
DELAY
P8.31
Auxiliary motor2
START/STOP
delay time
0.0~3600.0s
5.0s
○
MOTOR 2
DELAY
P8.32
Brake threshold
voltage
320.0~750.0V
700.0V
○
BRAK VOLT
P8.33
Low-frequency
threshold of
restraining
oscillation
0~9999
1000
○
LO FREQ
RESTRAIN
P8.34
High-frequency
threshold of
restraining
oscillation
0~9999
1000
○
HI FREQ
RESTRAIN
P9 Group: PID Control
P9.00
PID preset source
selection
0: Keypad
1: AI1
2: AI2
3: AI3
4: AI4
5: HDI1
6: HDI2
7: Communication
8: Simple PLC
0
○
PID PRESET
P9.01
Keypad PID
preset
0.0%~100.0%
0.0%
○
KEYPAD PID
SET