CHV100 Series Close Loop Vector Control Inverter
.72.
Setting
value
Function
Description
32~52
Reserved
Reserved for water supply control.
53
3-wire jog
control
Combine with FWD/REV operation to be 3-wire jog control.
K1
K2
K3
Command
ON
OFF
Forward running
OFF
ON
OFF
Reverse running
ON
OFF
Forward jogging
OFF
ON
ON
Reverse jogging
54~55
Reserved
Reserved
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.12
ON-OFF filter
times
1~10
1~10
5
This parameter is used to set filter strength of terminals (S1~S8,HDI1,HDI2). When
interference is heavy, user should increase this value to prevent malfunction.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.13
FWD/REV control
mode
0: 2-wire control mode 1
1: 2-wire control mode 2
2: 3-wire control mode 1
3: 3-wire control mode 2
0~3
0
This parameter defines four different control modes that control the inverter operation
through external terminals.
0: 2-wire control mode 1: Integrate START/STOP command with run direction.
K1
K2
Run command