CHV100 Series Close Loop Vector Control Inverter
.79.
Setting
Value
Function
Description
14
Upper frequency
limit reached
ON: Running frequency reaches the value of P0.08.
15
Lower frequency
limit reached
ON: Running frequency reaches the value of P0.09.
16
Ready
ON: Inverter is ready (no fault, power is ON).
17
Auxiliary motor 1
started
18
Auxiliary motor 2
started
In the case of simple water supply system with one
inverter driving three pumps, it is used to control
auxiliary pumps. For details, please refer to
descriptions of P8.29, P8.30 and P8.31.
19
Motor running
ON: Inverter has output signal
20
Stop pulse output
Output pulse signal for 2s when running frequency
is lower than 0.1Hz
21~31
Reserved
Reserved
Function
Code
Name
Description
Setting
Range
Factory
Setting
P6.07
AO1 function
selection
Multifunctional
analog
output
0~14
0
P6.08
AO2 function
selection
Multifunctional
analog
output
0~14
0
P6.09
HDO function
selection
Multifunctional high-speed
pulse output
0~14
0
AO/HDO output functions are indicated in the following table:
Setting
Value
Function
Range
0
Running frequency
0~maximum frequency (P0.07)
1
Reference frequency
0~ maximum frequency (P0.07)
2
Motor speed
0~2* rated synchronous speed of motor
3
Output current
0~2* inverter rated current
4
Output voltage
0~2* inverter rated voltage
5
Output power
0~2* rated power
6
Output torque
0~2*rated torque