CHV100 Series Close Loop Vector Control Inverter
.139.
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P8.13
Jitter frequency 0.0~50.0%
0.0%
○
JITTER
FREQ
P8.14
Rise time of
traverse
0.1~3600.0s
5.0s
○
TRAV RISE
TIME
P8.15
Fall time of
traverse
0.1~3600.0s
5.0s
○
TRAV FALL
TIME
P8.16
Auto reset times 0~3
0
○
AUTO
RESET
TIMES
P8.17 Fault relay action
0: Disabled
1: Enabled
0
○
FAULT
ACTION
P8.18
Reset interval 0.1~100.0s
1.0s
○
RESET
INTERVAL
P8.19
Preset length
1~65535
1000
○
PRESET
LENGTH
P8.20
Actual length
0~65535
0
○
ACTUAL
LENGTH
P8.21
Number of pulse
per cycle
0.1~6553.5
100.0
○
PULSE
NUMBER
P8.22
Preset count
value
1~65535
1000
○
PRESET
COUNT
P8.23
Specified count
value
1~65535
1000
○
SPECIFIED
COUNT
P8.24
Preset running
time
0~65535h
65535 h
○
RUNNING
TIME
P8.25
FDT level
0.00~ P0.07
50.00Hz
○
FDT LEVEL
P8.26
FDT lag
0.0~100.0%
5.0%
○
FDT LAG
P8.27
Frequency arrive
detecting range
0.0~100.0% (maximum
frequency)
0.0%
○
FAR RANGE
P8.28
Droop control 0.00~10.00Hz
0.00Hz
○
DROOP
CONTROL