CHV100 Series Close Loop Vector Control Inverter
.71.
Setting
value
Function
Description
21
ACC/DEC time
selection1
22
ACC/DEC time
selection 2
4 groups of ACC/DEC time can be selected by the
combination of these two terminals.
ACC/DEC time
selection 2
ACC/DEC time
selection1
ACC/DEC time
OFF
OFF
ACC/DEC time 0
(P0.11
、
P0.12)
OFF
ON
ACC/DEC time 1
(P8.00
、
P8.01)
ON
OFF
ACC/DEC time 2
(P8.02
、
P8.03)
ON
ON
ACC/DEC time 3
(P8.04
、
P8.05)
23
Reset simple
PLC when stop
When simple PLC stops, the status of PLC such as running
step, running time and running frequency will be cleared
when this terminal is enabled.
24
Pause simple
PLC
Inverter runs at zero frequency and PLC pauses the timing
when this terminal is enabled. If this terminal is disabled,
inverter will start and continue the PLC operation from the
status before pause.
25
Pause PID
PID adjustment will be paused and inverter keeps output
frequency unchanged.
26
Pause traverse
operation
Inverter keeps output frequency unchanged. If this terminal
is disabled, inverter will continue traverse operation from
current frequency.
27
Reset traverse
operation
Reference frequency of inverter will be forced as center
frequency of traverse operation.
28
Reset counter Clear the value of counter.
29
Reset length Clear the value of actual length (P8.20).
30
ACC/DEC
ramp hold
Pauses acceleration or deceleration and maintains output
frequency. When this terminal is disabled,
acceleration/deceleration is restarted.
31
Disable torque
control
Torque control is disabled. Inverter will work in speed
control mode.