Figure 6.31 Relationship between bias limit and output frequency.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P9.09
PID output filter
time
0.00~10.00s
0.00~10.00
0.00
The bigger the filter time, the better the immunity capability, but the response becomes
slow, vice versa.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P9.10
Feedback lost
detecting value
0.0~100.0%
0.0~100.0
0.0%
P9.11
Feedback lost
detecting time
0.0~3600.0s
0.0~3600.0
1.0s
When feedback value is less than P9.10 continuously for the period determined by P9.11,
the inverter will alarm feedback lost failure (PIDE).
Notice: 100% of P9.10 is the same as 100% of P9.01.
6.11 PA Group --Simple PLC and Multi-step Speed Control
Simple PLC function can enable the inverter change its output frequency and directions
automatically according to preset running time. For multi-step speed function, the output
frequency can be changed only by multi-step terminals.
Notice:
l
Simple PLC has 16 steps which can be selected.