CHV100 Series Close Loop Vector Control Inverter
.58.
Figure 6.6 DC braking diagram.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.13
Dead time of
FWD/REV
0.0~3600.0s
0.0~3600.0
0.0s
Set the hold time at zero frequency in the transition between forward and reverse
running.
It is shown as following figure:
Figure 6.7 FWD/REV dead time diagram.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.14
Action when
running frequency
is less than lower
frequency limit
0: Running at the lower
frequency limit
1: Stop
2: Stand-by
0~2
0
0: Running at the lower frequency limit (P0.09): The inverter runs at P0.09 when the
running frequency is less than P0.09.