CHV100 Series Close Loop Vector Control Inverter
.80.
Setting
Value
Function
Range
7
AI1 voltage
0~10V
8
AI2 voltage/current
0~10V/0~20mA
9
AI3 voltage
-10V~10V
10
AI4 voltage
0~10V
11
HDI1 frequency
0.1~50.0kHz
12
HDI2 frequency
0.1~50.0kHz
13
Length value
0~preset length (P8.19)
14
Count value
0~preset count value (P8.22)
Function
Code
Name
Description
Setting
Range
Factory
Setting
P6.10
AO1 lower limit
0.0%~100.0%
0.0~100.0
0.0%
P6.11
AO1 lower limit
corresponding
output
0.00V ~10.00V
0.00~10.00
0.00V
P6.12
AO1 upper limit
0.0%~100.0%
0.0~100.0
100.0%
P6.13
AO1 upper limit
corresponding
output
0.00V ~10.00V
0.00~10.00
10.00V
P6.14
AO2 lower limit
0.0%~100.0%
0.0~100.0
0.0%
P6.15
AO2 lower limit
corresponding
output
0.00V ~10.00V
0.00~10.00
0.00V
P6.16
AO2 upper limit
0.0%~100.0%
0.0~100.0
100.0%
P6.17
AO2 upper limit
corresponding
output
0.00V ~10.00V
0.00~10.00
10.00V
These parameters determine the relationship between analog output voltage/current and
the corresponding output value. When the analog output value exceeds the range
between lower limit and upper limit, it will output the upper limit or lower limit.
When AO is current output, 1mA is corresponding to 0.5V.
For different applications, the corresponding value of 100.0% analog output is different.
For details, please refer to description of each application.