CHV100 Series Close Loop Vector Control Inverter
.78.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P6.03
HDO ON-OFF
output selection
Open-collector output
0~31
0
P6.04
Relay 1 output
selection
Relay output
0~31
3
P6.05
Relay 2 output
selection
Relay output
0~31
0
P6.06
Relay 3 output
selection
Relay output
0~31
0
OC/Relay output functions are indicated in the following table:
Setting
Value
Function
Description
0
No output
Output terminal has no function.
1
Run forward
ON: During forward run.
2
Run reverse
ON: During reverse run.
3
Fault output
ON: Inverter is in fault status.
4
Motor overload
Please refer to description of PB.04~PB.06.
5
Inverter overload
Please refer to description of PB.04~PB.06.
6
FDT reached
Please refer to description of P8.25, P8.26.
7
Frequency
reached
Please refer to description of P8.27.
8
Zero speed
running
ON: The running frequency of inverter is zero.
9
Preset count value
reached
Please refer to description of P8.22.
10
Specified count
value reached
Please refer to description of P8.23.
11
Length reached
ON: Actual length (P8.20) reaches the value of
P8.19.
12
PLC cycle
completed
After simple PLC completes one cycle, inverter will
output ON signal for 200ms.
13
Running time
reached
ON: The accumulated running time of inverter
reaches the value of P8.24.