CHV100 Series Close Loop Vector Control Inverter
.23.
external braking unit between (+) and (-).
4.
+24V connect with PW as default setting. If user need external power supply,
disc24V with PW and connect PW with external power supply.
4.4 Specifications of Breaker, Cable, Contactor and Reactor
4.4.1 Specifications of breaker, cable and contactor
Model No.
Circuit
breaker (A)
Input/output cable
(mm
2
)
(Coppery wire)
Rated current of
contactor (A)
(380V or 220V)
3AC 220V
±
15%
CHV100-0R7G-2
16
2.5
10
CHV100-1R5G-2
20
4
16
CHV100-2R2G-2
32
6
20
CHV100-004G-2
40
6
25
CHV100-5R5G-2
63
6
32
CHV100-7R5G-2
100
10
63
CHV100-011G-2
125
25
95
CHV100-015G-2
160
25
120
CHV100-018G-2
160
25
120
CHV100-022G-2
200
35
170
CHV100-030G-2
200
35
170
CHV100-037G-2
200
35
170
CHV100-045G-2
250
70
230
3AC 380V
±
15%
CHV100-1R5G-4
16
2.5
10
CHV100-2R2G-4
16
2.5
10
CHV100-004G-4
25
4
16
CHV100-5R5G-4
25
4
16
CHV100-7R5G-4
40
6
25
CHV100-011G-4
63
6
32
CHV100-015G-4
63
6
50
CHV100-018G-4
100
10
63
CHV100-022G-4
100
16
80