CHV100 Series Close Loop Vector Control Inverter
.124.
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P3.05
ASR switching
point 2
P3.02~P0.07
10.00Hz
○
ASR
SWITCHPOI
NT2
P3.06
ACR proportional
gain P
0~65535
500
○
ACR P
P3.07
ACR integral gain
I
0~65535
500
○
ACR I
P3.08
Speed detection
filter time
0.00~5.00s
0.00s
○
FEEDBACK
FILTER
P3.09
Slip
compensation
rate of VC
50.0~200.0%
100%
○
VC SLIP
COMP
P3.10
PG parameter 1~65535
1000
◎
PG
PARAMETER
P3.11
PG direction
selection
0:Forward
1:Reverse
0
◎
PG
DIRECTION
P3.12
Torque setting
source
0:Disabled
1: Keypad
2:AI1
3:AI2
4:AI3
5:AI4
6:HDI1
7:HDI2
8:Communication
0
○
TORQUE
SETTING
P3.13
Keypad torque
setting
-100.0%~100.0%
50.0%
○
KEYPAD
TORQUE
SET
P3.14
Torque limit
0.0~200.0%(rated current
of inverter)
150.0%
○
TORQUE
LIMIT
P4 Group: V/F Control