CHV100 Series Close Loop Vector Control Inverter
.42.
P2.03: motor rated voltage;
P2.04: motor rated current
P2.05: motor rated power.
Notice: the motor should be uncoupled with its load; otherwise, the motor
parameters obtained by autotuning may be not correct.
Set P0.17 to be 1, and for the detail process of motor parameter autotuning, please refer
to the description of Function Code P0.17. And then press RUN on the keypad panel,
the inverter will automatically calculate following parameter of the motor:
P2.06: motor stator resistance;
P2.07: motor rotor resistance;
P2.08: motor stator and rotor inductance;
P2.09: motor stator and rotor mutual inductance;
P2.10: motor current without load;
then motor autotuning is finished.
5.2.6 Password setting
CHV series inverter offers user
’
s password protection function. When P7.00 is set to be
nonzero, it will be the user
’
s password, and After exiting function code edit mode, it will
become effective after 1 minute. If pressing the PRG/ESC again to try to access the
function code edit mode,
“
-----
”
will be displayed, and the operator must input correct
user
’
s password, otherwise will be unable to access it.
If it is necessary to cancel the password protection function, just set P7.00 to be zero.
Notice: Password is not effective for parameters in shortcut menu.
5.3 Running State
5.3.1 Power-on initialization
Firstly the system initializes during the inverter power-on, and LED displays
“
8.8.8.8.8
”
.
After the initialization is completed, the inverter is on stand-by status.
5.3.2 Stand-by
At stop or running status, parameters of multi-status can be displayed. Whether or not to
display this parameter can be chosen through Function Code P7.06 (Running status
display selection ) and P7.07 (Stop status display selection) according to binary bits, the
detailed description of each bit please refer the function code description of P7.06 and
P7.07.
In stop status, there are fourteen parameters which can be chosen to display or not.
They are: reference frequency, DC bus voltage, Input-Output terminal status, open