CHV100 Series Close Loop Vector Control Inverter
.89.
Rise time of traverse: Indicates the time rising from the lowest traverse frequency to the
highest traverse frequency.
Fall time of traverse: Indicates the time falling from the highest traverse frequency to the
lowest traverse frequency.
Notice:
l
P8.12 determines the output frequency range which is as below:
(1-P8.12%) * reference frequency
≤
output frequency
≤
(1+P8.12%) *
reference frequency
l
The output frequency of traverse is limited by upper frequency limit (P0.08)
and lower frequency limit (P0.09).
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.16
Auto reset times 0~3
0~3
0
P8.17
Fault relay action
0: Disabled
1: Enabled
0~1
0
P8.18
Reset interval
0.1~100.0s
0.1~100.0
1.0s
Auto reset function can reset the fault in preset times and interval. When P8.16 is set to
be 0, it means
“
auto reset
”
is disabled and the protective device will be activated in case
of fault.
P8.17 defines if fault relay active or not during auto reset. If continuous production
without interruption is needed, please set P8.17=0.
Notice:
l
The fault such as OUT 1, OUT 2, OUT 3, OH1 and OH2 cannot be reset
automatically.
l
If fault has not occurred for ten minutes after the fault is reset, inverter will
automatically clear the previous times of auto reset.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.19
Preset length
1~65535
1~65535
1000
P8.20
Actual length
0~65535
0~65535
0
P8.21
Number of pulse
per cycle
0.1~6553.5
0.1~6553.5
100.0
These parameters are mainly used for fixed-length control.
The length is calculated by input pulse signal. If input pulse frequency is high, it is
required to use HDI1 or HDI2 input (P5.35 or P5.36 = 2)