CHV100 Series Close Loop Vector Control Inverter
.100.
l
If P0.03 is set to be 5, 16 steps are available for multi-step speed. Otherwise
only 15 steps are available (step 1~15).
Function
Code
Name
Description
Setting
Range
Factory
Setting
PA.00
Simple PLC mode
0: Stop after one cycle
1: Hold last frequency after
one cycle
2: Circular run
0~2
0
0: Stop after one cycle: Inverter stops automatically as soon as it completes one cycle,
and it is needed to give run command to start again.
1: Hold last frequency after one cycle: Inverter holds frequency and direction of last step
after one cycle.
2: Circular run: Inverter continues to run cycle by cycle until receive a stop command.
Figure 6.32 Simple PLC operation diagram.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PA.01
Simple PLC status
saving selection
0: Not saved
1: Saved
2: Not saved when power
off, saved when stop
0~1
0
This parameter determines whether the running step and output frequency of simple
PLC should be saved. If PA.01 is set to be 2, running step and output frequency will be
saved when inverter stops, but will not be saved when inverter is power off.