CHV100 Series Close Loop Vector Control Inverter
.63.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P3.11
PG direction
selection
0: Forward
1: Reverse
0~1
0
P3.10 defines the number of pulse per cycle of PG or encoder.
Notice: When P0.00 is set to be 1, P3.10 must be set correctly according to the
encoder parameter, otherwise the motor will run abnormally. If the motor still run
abnormally when P3.10 has been set correctly, please change the PG direction
(P3.11).
Function
Code
Name
Description
Setting Range
Factory
Setting
P3.12
Torque setting
source
0:Disabled
1: Keypad
2:AI1
3:AI2
4:AI3
5:AI4
6:HDI1
7:HDI2
8:Communication
0~8
0
P3.13
Keypad torque
setting
-100.0%~100.0%
-100.0%~100.0% 50.0%
P3.14
Torque limit
0.0~200.0%
0.0~200.0
150.0%
0
:
Torque control is disabled. Inverter will run at speed control mode. Output torque of
inverter which should not greater than torque limit (P3.14) matches the torque of load
automatically. When the torque of load is greater than torque limit, output torque will
remain as torque limit and output frequency will decrease automatically.
1~8: Torque control is enabled.
l
When torque control takes effect,
if T
set
> T
load
, output frequency will increase continuously until it reaches upper
frequency limit.
If T
set
< T
load,
output frequency will decrease continuously until it reaches lower
frequency limit.
Inverter can run at any frequency between upper and lower frequency limit only
when T
set
= T
load.