Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
- 60 -
HD3N Series User Manual V1.1
Ref. code
Function Description
Setting Range [Default]
F04.19
REV frequency upper limit of PID output
0.0 - 100.0 [100.0%]
Defines the frequency upper limit when reverse at PID. It is valid when F04.18 = 1 (permit REV).
•
When PID serves as aux frequency setting channel, F04.19 is invalid, upper limit is set by F19.35 and
F19.36.
F04.20
Proportional gain (P2)
0.0 - 500.0 [50.0]
F04.21
Integral time (I2)
0.01 - 10.00 [1.00s]
F04.22
Differential time (D2)
0.00 - 10.00 [0.00s]
F04.23
PID parameter adjustment bases
0 - 3 [0]
0: Do not adjust. Second PID is invalid.
1: DI.
•
Switch PID parameter according to DI terminal No. 59 function. When the terminal is invalid, select
group 1 (F04.04, F04.05, F04.07); when valid, select group 2 (F04.20 - F04.22).
2: Bias.
•
Select group 2 when bias between PID feedback and PID setting< switching point 1 (F04.24);
•
Select group 1 when bias between PID feedback and PID setting> switching point 1 (F04.25);
•
Select linear interpolation when bias between PID feedback and PID setting is within switching point 1
and 2.
3: Frequency.
•
Select group 1 when PID output frequency<switching point 1 (F04.24);
•
Select group 2 when PID output frequency> switching point 2 (F04.25);
•
Select linear interpolation when PID output frequency is within switching point 1 and 2.
F04.24
PID parameter switching point 1
0.0 - F04.25 [0.0%]
F04.25
PID parameter switching point 2
F04.24 - 100.0 [100.0%]
F04.27
Rpm
1 - 9999 [1024]
F04.28
Max. closed-loop speed
1 - 24000 [1500rpm]
F04.29
PID calculating mode
0,1 [0]
0: Do not calculate when HD3N stops.
1: Calculate when HD3N stops.
F04.30
PID dormancy selection
0,1 [0]
0: Disable.
1: Enable.
F04.31
Wakeup tolerance
0.0 - 100.0 [10.0%]
F04.32
Wakeup delay
0.0 - 6000.0 [0.0s]
Positive: in dormant status, when feedback
≤
setting
×
(100% - F04.31), and counting time
≥
F04.32, wake
up HD3N;
Negative: in dormant status, when feedback
≥
setting
×
(100% + F04.31), and counting time
≥
F04.32, wake
up HD3N.
F04.33
Dormancy tplerance
0.0 - 100.0 [10.0%]
F04.34
Dormancy delay
0.0 - 6000.0 [0.0s]
F04.35
Dormancy frequency
0.00 - max. frequency
[20.00Hz]
Positive: in wakeup status, when feedback
≥
setting
×
(100% + F04.33), target frequency
≤
F04.35 and
counting time
≥
F04.34, HD3N is dormant;
Negative: in wakeup status, when feedback
≤
setting
×
(100% - F04.33), target frequency
≤
F04.35 and
counting
≥
F04.34, HD3N is dormant.