Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
- 46 -
HD3N Series User Manual V1.1
6.1
Group d: Display Parameter
Group d is status display parameter.
6.1.1
d00: Status Display Parameter
Ref. code
Function Description
Setting Range [Default]
d00.00
HD3N series
[Actual value]
d00.01
Software version of HD3N
[Actual value]
d00.03
Non-standard software version of HD3N
[Actual value]
d00.05
Software version of keypad
[Actual value]
Valid only when LED keypad adopted.
d00.06
Customized serial number
[Actual value]
d00.07
Motor and control mode
[Actual value]
Displays present motor and control mode.
Unit: Unused
Ten: Control mode
•
0: V/f control without PG.
•
2: Vector control without PG.
d00.08
Rated current of HD3N (A)
[Actual value]
d00.10
Inverter status
[Actual value]
Displays the inverter status, as following:
Thous
ands
Bit15: Unused
Bit14: Hardware
current restriction
0: Do not restrict
1: Restrict
Bit13: Software
current restriction
0: Do not restrict
1: Restrict
Bit12: Stall
overvoltage
0: Invalid
1: Valid
Hundr
eds
Bit11: Control mode
0: Speed control
1: Torque control
Bit10: Speed
limitation
0: Below limitation
1: Above limitation
Bit9: Unused
Bit8: Auto-tuning
0: Not in auto-tuning
1: In suto-tuning
Tens
Bit7: DC brake
0: Invalid
1: Valid
Bit6: Unused
Bit5&Bit4: Acc. / Dec./Constant
00: Constant
11: Constant
01: Acc
10: Dec
Units
Bit3: Zero speed
0: Invalid
1: Valid
Bit2: Forward/Reverse
0: Forward
1: Reverse
Bit1: Run/Stop
0: Stop
1: Run
Bit0: Inverter fault
0: Faulty
1: Normal
123
d00.11
Main setting frequency channel
[Actual value]
0: Keypad.
1: Terminal.
2: Communication.
3: Analogue.
4: Terminal pulse.
6 - 7: AI1 - AI2.
10: Potentionmeter on keypad.
11: PID.
12: Multi-speed.
13: PLC.
14: Wobble.
d00.12
Main setting frequency (Hz)
[Actual value]
d00.13
Aux setting frequency (Hz)
[Actual value]
d00.14
Setting frequency (Hz)
[Actual value]
d00.15
Setting frequency (after Acc. / Dec.) (Hz)
[Actual value]
Display the setting frequency after Acc. / Dec..