Shenzhen Hpmont Technology Co., Ltd.
Appendix B Communication Protocol
HD3N Series User Manual V1.1
- 149 -
Status parameter (0x33) address mapping
The status parameters (0x33) are mapped as higher bytes of the register address, and the intergroup
indexes are as following:
Address
Function
Address
Function
0x3300
Controller series
0x331C
AI1input voltage (after calculating)
0x3301
Software version of DSP
0x331D
AI2 input voltage
0x3303
Special sofwtware ersion of MCB
0x331E
AI2 input voltage (after calculating)
0x3305
Software of keypad
0x3323
DI6 terminal pulse input frequency
0x3306
Customized serial No.
0x3324
AO1 output
0x3307
Motor and control mode selection
0x3325
AO2 output
0x3308
Rated current of inverter
0x3326
High speed output pulse frequency
0x330A
Inverter status
0x332C
Process PID setting
0x330B
Main setting frequency channel
0x332D
Process PIDfeedback
0x330C
Main setting frequency
0x332E
Process PID tolerance
0x330D
Aux setting frequency
0x332F
Process PID integral
0x330E
Setting frequency
0x3330
Process PID output
0x330F
Setting frequency (after calculated)
0x3331
External counting value
0x3310
Output frequency
0x3332
Input terminal status
0x3311
Setting rpm
0x3333
Output terminal status
0x3312
Running rpm
0x3334
MODBUS status
0x3313
Input cable voltage
0x3335
Actrual length
0x3314
Output voltage
0x3336
Accumulative length
0x3315
Output current
0x3337
Total power up time
0x3316
Torque setting
0x3338
Total running time
0x3317
Output torque
0x3339
Total energy consumption high bit of
motor
0x3318
Output frequency
0x333A
Total energy consumption low bit of
motor
0x3319
DC busbar voltage
0x333B
Present energy consumption high bit
0x331A
Input voltage of potentionmeter
0x333C
Present energy consumption low bit
0x331B
AI1 input voltage
0x333D
Present fault
5.
Special Instruction
1. Host computer cannot restore to factory setting. It can read but not write these parameters: F08
(Asyn motor parameter) and F17 (SCI parameter).
2. Host computer cannot modify F01.00 (user password). But it can write F01.00 to verify user
password. When verified, host computer access modifying function parameter of inverter. After
modifying, write invalid password into F01.00 to disable this access.
3. If many multi-function input terminals setting are the same, it may cause dysfunction. Therefore, the
user should avoid this case when modify the multi-function terminal function via the MODBUS.
B