Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd.
- 118 -
HD3N Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F04.01
Setting channel selection
0: Digital
1: Analogue
2: Terminal pulse
3 - 4: AI1 - AI2
7: Potentionmeter ( LED keypad)
0
1
×
F04.02
Feedback channel
selection
0: Analogue
1: Terminal pulse
2: AI1 - AI2
6: Potentionmeter (LED keypad)
7: Speed closed-loop
0
1
×
F04.03
Setting digital reference
-100.0 - 100.0%
0.0%
0.1%
○
F04.04
Proportional gain (P1)
0.0 - 500.0
50.0
0.1
○
F04.05
Integral time (I)
0.01 - 10.00s
1.00s
0.01s
○
F04.06
Integral upper limit
0.0 - 100.0%
100.0%
0.1%
○
F04.07
Differential time (D1)
0.00 - 10.00s
0.00s: F04.07 is invalid
0.00s
0.01s
○
F04.08
Differential upper limit
0.0 - 100.0%
20.0%
0.1%
○
F04.09
Sampling time (T)
0.01 - 50.00s
0.10s
0.01s
○
F04.10
Bias limit
0.0 - 20.0% (setting)
0.0%
0.1%
○
F04.11
Upper limit channel of PID
regulator
0: Set by F04.13
1: Analogue
2: Terminal pulse
3 - 4: AI1 - AI2
7: Potentionmeter ( LED keypad)
0
1
×
F04.12
Lower limit channel of PID
regulator
0: Set by F04.14
1: Analogue
2: Terminal pulse
3 - 4: AI1 - AI2
7: Potentionmeter ( LED keypad)
0
1
×
F04.13
PID regulator upper limit
0.0 - 100.0%
100.0%
0.1%
×
F04.14
PID regulator lower limit
0.0 - 100.0%
0.0%
0.1%
×
F04.15
Regulating characteristic
of PID regulator
0: Positive characteristic
1: Negative characteristic
0
1
×
F04.17
PID output filtering time
0.01 - 10.00s
0.05s
0.01s
○
F04.18
REV selection when PID
outputs
0: Prohibit REV when PID regulates
1: Permit REV
0
1
×
F04.19
REV frequency upper limit
of PID output
0.0 - 100.0%
100.0%
0.1%
×
F04.20
Proportional gain (P2)
0.0 - 500.0
50.0
0.1
○
F04.21
Integral time (I2)
0.01 - 10.00s
1.00s
0.01s
○
F04.22
Differential time (D2)
0.00 - 10.00s
0.00s
0.01s
○
F04.23
PID parameter adjustment
bases
0: Do not adjust
1:DI
2: Bias
0
1
○