3.3
Installation Direction and Space
To achieve good cooling efficiency, install HD3N
perpendicularly and always provide the following space
to allow normal heat dissipation.
The space are shown in Table 3-1.
Table 3-1 Installation space
Inverter power
≤
55kW
≥75kW
A (Left/Right)
≥50mm
≥150mm
B (UP/Down)
≥100mm
≥350mm
C (Upper air-vent )
≥50mm
≥100mm
D (Lower air-vent)
≥50mm
≥100mm
123
When one inverter is mounted on top of another, an air flow
diverting plate should be fixed between them. Just as shown
in Table 3-2.
Table 3-2 Installation of several inverters
Inverter power
≤
55kW
≥75kW
A
≥50mm
≥100mm
B
≥50mm
≥100mm
C
≥50mm
≥100mm
a
≥50mm
≥100mm
b
≥50mm
≥100mm
c
≥50mm
≥100mm
123
C
C
B
D
D
B
A
A
C
B
a
b
c
A