Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD3N Series User Manual V1.1
- 67 -
Ref. code
Function Description
Setting Range [Default]
F07.02
Wobble preset frequency
0.00 - F00.08 [0.00Hz]
F07.03
Waiting time for wobble preset frequency
0.0 - 999.9 [0.0s]
F07.02 defines running frequency of HD3N before entering wobble sate.
F07.03 defines the duration of F07.02 before entering wobble state.
•
Valid when F07.01 units = 0.
F07.04
Wobble value
0.0 - 50.0 [0.0%]
Calculated from wobble centric frequency: F
W
= centric frequency × F07.04.
•
Wobble centric frequency is a value set by F00.10 (frequency setting channel selection).
Calculated from max. Output frequency: FW = max. Output frequency F00.06 × F07.04.
F07.05
Skip frequency
0.0 - F07.04 [0.0%]
It is percentage from wobble value. F07.05 = 0, there is no skip frequency.
F07.06
Wobble period
0.1 - 999.9 [10.0s]
Defines the time during which wobble goes up and down.
F07.07
Triangular wave rising time
0.0 - 100.0 [50.0%]
Defines the running times that wobble rise and fall. It relates to F07.06. Unit: s.
•
Running time at rising = F07.06 × F07.07.
•
Running time at falling = F07.06 × (1 - F07.07).
6.2.9
F08: Asyn. Motor Parameters
Formula of mutual inductance:
Mutual inductance F08.10 =
F08.01
2
√
3
π
× F08.03 × F08.11
−
F08.09
Ref. code
Function Description
Setting Range [Default]
F08.00
Rated power of motor
0.2 - 500.0kW [Depend on HD3N]
F08.01
Rated voltage of motor
0 - 999V [Depend on HD3N]
F08.02
Rated current of motor
0.1 - 999.9A [Depend on HD3N]
F08.03
Rated frequency of motor
1.0 - 400.0 [50.0Hz]
F08.04
Rated Rpm of motor
1 - 24000rpm [Depend on HD3N]
F08.00 - F08.04: Set rated value of motor according to motor nameplate.
L
m
R1=F08.07 (Stator resistance)
R2=F08.08 (Rotor resistance)
Io=F08.11 (Excitation current)
R1
R2
LI
I1
I2
S
1-S
R2
LI
LI=F08.09 (Leakage inductance)
Lm=F08.10 (Mutual inductance)
S=Slip ratio
U1
Io
6