Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd.
- 134 -
HD3N Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F19: Function-boost Parameters (on pages 88 - 95)
F19.00
Aux frequency setting
source selection
0: No aux channel
1: Keypad
2: Terminal
3: SCI
4: Analogue
5: Terminal puse
6: PID output
7: AI1
8: AI2
11: Potentionmeter (LED keypad)
0
1
○
F19.01
Main/Aux setting
calculating
Unit: Main/Aux calculating
0: Main+Aux setting
1: Main-Aux setting
Ten: Frequency source selection
0: Main
1: Main/Aux calculating
2: Main/Aux switching
3: Main and Main/Aux calculating
switching
4: Aux and Main/Aux calculating
switching
10
1
○
F19.02
Aux setting coefficient
0.00 - 9.99
1.00
0.01
○
F19.03
Initial value of digital aux
frequency
0.00 - F00.06
0.00Hz
0.01Hz
○
F19.04
Digital aux frequency
control
Unit: Storage selection at power
failure
0: Do not save aux frequency
1: Save aux frequency
Ten: Frequency at stop
0: Maintain aux frequency at stop
1: Aux frequency resumes to F19.03
at stop
00
1
○
F19.05
Setting frequency
adjustment selection
0: Do not adjust
1: Adjust according to max. output
frequency (F00.06)
2: Adjust according to current
frequency
1
1
○
F19.06
Setting frequency
adjustment coefficient
0.0 - 200.0%
100.0%
0.1%
○
F19.07
Fan control
0: Auto stop
1: Immediate stop
2: Runs all the time when power on
0
1
○
F19.08
Fan control delay time
0.0 - 600.0s
60.0s
0.1s
○