Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD3N Series User Manual V1.1
- 51 -
Ref. code
Function Description
Setting Range [Default]
F00.14
Frequency setting control
0000 - 1111 [1001]
Units and tens are valid only when F00.10 = 0 or 1.
The current setting frequency value will be replaced by a new one when F00.13 has been changed.
Unit: Save selection of frequency setting at power
outage
•
0: Do not save at power outage.
•
1: Save at power outage.
Ten: Control selection of frequency setting at stop
•
0: Set frequency is kept in stop.
•
1: Restore to F00.13 at stop.
Hundred: Save selection of communication setting
frequency
•
0: Do not save at power outage.
•
1: Save at power outage.
Thousand: Save selection of frequency setting
when switching frequency source
•
0: Do nto save.
•
1: Save. When frequency setting source swicthes
from keypad -> terminal digital setting –> keypad,
setting on keypad do not change.
F00.15
Jog running frequency digital setting 1
0.00 - upper limit
frequency [5.00Hz]
F00.16
Interval of jog running
0.0 - 100.0 [0.0s]
After cancel jog command, HD3N will not respond
to jog command within F00.16.
•
After the interval of jog is completed, it
immediately executes the arrived jog
command. As show in figure.
F00.17
Running direction
0,1 [0]
0: The same as running command.
1: Opposite to running command.
F00.18
Reverse
0,1 [0]
This function is valid when F00.11 = 0,1,2.
0: Permitted.
1: Prohibitted.
•
HD3N responds to FWD/REV commands only. If frequency < 0Hz, HD3N will run at zero-frequency.
•
HD3N will not responds to FWD/REV commands at stop status; during running, if HD3N receives REV
command, it will accelerates to stop status.
•
Simple PLC runs to setting range of REV, HD3N will accelerates and run at zero-speed. It will not resume
running until meeting FWD setting range.
F00.19
Dead time of direction switch
0.0 - 3600.0 [0.0s]
Defines the dead time of direction switch, namely, the time of zero-frequency output in the process of
direction switch.
F00.20
Enable key operation of keypad
0,1 [0]
0: Enable. When LCD and LED keypads are connected to HD3N, LED keypad can operate.
1: Invalid. When LCD and LED keypads are connected to HD3N, LED keypad can not operate.
F00.21
Dormant function
0,1 [0]
0: Disabled. This function is invalid.
1: Enable.
F00.16
Jog running
frequency
Time
Time
Jog command
Acc
Dec
Frequency
6