Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd.
- 140 -
HD3N Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F20.35
NO.2 fault interval
0 - 6553.5 hours
0.0h
0.1h
*
F20.36
NO.1 fault type
0 - 99
0
1
*
F20.37
NO.1 fault interval
0 - 6553.5 hours
0.0h
0.1h
*
F20.38
Last time fault interval
0 - 6553.5 hours
0.0h
0.1h
*
F21: Torque Control Parameter ( on pages 98 - 99)
F21.00
Torque command setting
source selection
0: F21.01 digital
1: Analogue
2: Terminal puls
3: SCI communication
0
1
×
F21.01
Torque command digital
setting
-100.0 - 100.0% (F21.02)
0.0%
0.1%
○
F21.02
Max. torque setting
0.0 - 500.0% (rated torque of motor)
100.0%
0.1%
×
F21.03
Filtering time of torque
command
0.000 - 1.000s
0.000s
0.001s
○
F21.04
Speed control under
torque control
0: Set by F21.05 and F21.06
1: Set by F00.06
2: Set by analogue limit
1
1
×
F21.05
Forward speed limit under
torque control
0 - 100% (F00.06)
100%
1%
○
F21.06
Reverse speed limit under
torque control
0 - 100% (F00.06)
100%
1%
○
F21.10
Stop mode selection
under torque control
0: Decelerates to stop + DC brake
1: Stop torque output
2: Coast to stop
0
1
×
F23: PWM Control Parameter (on pages 99 - 100)
F23.00
Carrier frequency
1 - 8kHz
6kHz
1kHz
×
F23.01
Auto adjust carrier
frequency
0: Prohibited
1: Adjust 1
2: Adjust 2
1
1
×
F23.02
PWM overshoot enable
0: Disabled
1: Enabled
1
1
×
F23.03
PWM modulation mode
0: Switch between two phase/three
phase
1: Three phase
0
1
×
F23.04
Switch point 1 of PWM
modulation mode
5.00 - 50.00Hz
Depend
on HD3N
0.01Hz
×
F23.05
Switch point 2 of PWM
modulation mode
7.00 - 50.00Hz
Depend
on HD3N
0.01Hz
×
F23.09
Random carrier factor K1
0 - 2000
2
1
×
F23.10
Random carrier factor K2
0 - 2000
3
1
×
R02: Analogue Parameter Correction Factor ((on pages 100 - 100)
R02.00
AI1 display voltage 1
0.0 - 100.0%
0
R02.01
AI1 actual voltage 1
0.00 - 10.00V
0
R02.02
AI1 display voltage 2
0.0 - 100.0%
0