Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd.
- 130 -
HD3N Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
1: Report external fault (E0024), can
not auto reset.
2: Report external fault (E0024), can
auto reset
F15.40
Upper limit of exceeded
analogue input
F15.41 - 100.0%
100.0%
0.1%
○
F15.41
Lower limit of exceeded
analogue input
0.0% - F15.40
0.0%
0.1%
○
F15.42
Detection time for
exceeded analogue
0.00 - 50.00s
5.00s
0.01s
○
F15.43
Terminal output delay
0.0 - 100.0s
0.0s
0.1s
○
F15.44
Detection time for
exceeded analogue at
start
0.00 - 50.00s
15.00s
0.01s
○
F16: Analogue I/O Terminal Parameters (on pages 83 - 86)
F16.00
Keypad with
potentiometer function
0: Used
1: Upper frequency setting
2: Frequency setting
3: Aux frequency setting
4: Process PID setting
5: Process PID feedback
6: Process PID regulating upper limit
7: Process PID regulating lower limit
9: Electric torque limit when motor is
forward
10: Electric torque limit when motor
is reverse
11: Re-generative torque when
motor is forward
12:Re-generative torque when motor
is reverse
13: Torque command setting
15: Upper limit frequency in torque
control
0
1
×
F16.01
AI1 function
2
1
×
F16.02
AI2 function
5
1
×
F16.05
AI1 bias
-100.0 - 100.0%
0.0%
0.1%
○
F16.08
AI2 bias
-100.0 - 100.0%
0.0%
0.1%
○
F16.06
AI1 gain
0.00 - 10.00
1.00
0.01
○
F16.09
AI2 gain
0.00 - 10.00
1.00
0.01
○
F16.07
AI1 filtering time
0.01 - 10.00s
0.05s
0.01s
○
F16.10
AI2 filtering time
0.01 - 10.00s
0.05s
0.01s
○
F16.17
Max. input pulse
frequency
0 - 10000Hz
10000Hz
1Hz
○
F16.18
Input pulse filter time
0.01 - 10.00s
0.20s
0.01s
○