Chapter 4 Electrical Installation
Shenzhen Hpmont Technology Co., Ltd.
- 24 -
HD3N Series User Manual V1.1
Note:
Limit the current within 3A if relay terminal is to connect to AC 220V voltage signal.
4.4.2
Control Terminal (90 - 400kW)
Figure 4-2 Control board terminal (90 - 400kW)
Table 4-7 Control board terminal description (90 - 400kW)
Terminal
Description
+10, GND
+10V power supply
Analogue input use +10V power supply, max. output current is 100mA
GND is isolated to COM
AI1, AI2
Anglogue input
AI1 input voltage: 0 - 10V (input impedance: 34kΩ)
AI2 input voltage: -10V - 10V (input impedance: 34kΩ)
AI2 input current: 0 - 20mA (input impedance: 500Ω)
•
AI2, AI3 can select voltage/current
AO1, AO2
Anglogue output
Output voltage/current signal: 0 - 10V/0 - 20mA
Programmable output
GND
Anglogue ground
DI1 - DI6
Digital input
Programmable bipolar optional input signal
Input voltage: 0 - 30VDC
DI1 - DI5 input impedance: 4.7kW, DI6 input impedance: 1.6kΩ
•
DI6 can be selectable for high-frequency input, max-frequency
50kHz
P24, COM
Digital power supply
Digital input use +24V as supply, max. output current is 200mA
COM is isolated to CME
SEL
Digital input common
terminal
SEL and P24 are connected by default (factory setting)
•
Disconnect SEL and P24 when use external power to drive DI
DO1, CME
Digital output
Programmable optocoupler isolation
•
DO1, DO2 open collector output, output voltage: 0 - 30VDC, max.
output current 50mA
•
DO2 can be selectable for high-frequency output, max-frequency
50kHz
CME is isolated to COM, shortly connected to COM by default
•
Disconnect CME and COM when they are isolating output
DO2, COM
Digital output
+10
AI1
AI2
DI1
DI2
DI3
DI4
DI5
DI6 COM
R1A
COM
GND
AO1 AO2 P24
SEL
DO1
R1C
GND
COM CME
DO2 R1B
Control Board
Terminal