Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
- 80 -
HD3N Series User Manual V1.1
Ref. code
Function Description
Setting Range [Default]
14: Upper/Lower limit of wobble.
•
Indicating signal will output if wobble frequency range based on central frequency exceeds upper or
lower limit (F00.09).
•
Valid when F07.00 = 1.
15: Running in simple PLC mode. HD3N is in simple PLC running state.
16: Pause simple PLC running. When paused, output signal.
17: Simple PLC loop done. When done, output signal.
18: Simple PLC phase running is finished. When finished, output signal.
19: Simple PLC running is finished. When finished, output signal.
20: Signal output from SCI.
•
SCI control open collector output terminal or relay to output signal.
21: Set fully met running time.
•
When present accumulative running time meets set running times (F15.36), output signal.
Note: Output indicating signal of 17,18,19,21 function is single pulse signal, 500ms width.
22: Timing function. Output terminal of timing function.
•
Refer to F15.25, F15.26.
23: Set fully counting value.
24: Specific fully counting value.
•
Refer to F15.37, F15.38.
25: Set length.
•
Actual length = setting length, output indicating signal under length control.
27: Analogue input exceeding limit.
•
When analogue exceeds upper or lower limit, output indicating signal. Refer to F15.39 - F15.42.
29: Stop in under-voltage condition.
•
When DC busbar voltage is lower than under-voltage level, output indicating signal.
•
”-Lu-” is displayed on LED keypad.
30: Overload detection signal.
•
When output current of HD3N > F20.01 (overload pre-alarm detection value), and time > F20.02
(overload pre-alarm detection time), output indicating signal.
31: Inverter fault. HD3N has fault.
32: External fault. HD3N detects external devcice has fault via terminal.
33: Fault of inverter is reset automatically.
35: Dormancy function.
36: System is running.
•
When U/V/W terminals have output signal or waiting for starting status, output indicating signal.
•
Waiting for starting includes: dormancy, stop after analogue exceeding limit, stop caused by external
signal lost, stop by fault automatically reset,stop at zero frequency and and stop at power failure.
Running frequency Before limiting
amplitude
After limiting
amplitude
Central frequency
Upper limit of frequency
Time
Out signal
limitation of upper/lower limits
of wobble frequency