Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD3N Series User Manual V1.1
- 49 -
6.2
Group F: General Parameters
6.2.1
F00: Basic Parameters
Ref. code
Function Description
Setting Range [Default]
F00.00
Motor control mode
0,1 [0]
0: Speed control.
1: Torque control.
•
Torque control is valid only when motor control mode = 2 (F00.01 = 2).
•
Refer to group F15 DI terminal (No. 56/57 function) for detail description of torque control and group
F21 for torque control parameter.
F00.01
Motor control mode
0 - 2 [0]
0: V/f control without PG. Constant control voltage/frequency rate.
•
It is applicable for occasions when one inverter drives more than one motors to achieve proper
efficiency.
•
When select V/f control, please properly set the V/f control Group F09 to achieve proper efficiency.
2: Vector control without PG. (SVC control)
•
It is applicable for application with high requirement on inverter performance and torque.
•
At first, it must perform motor parameter auto-tuning. And then adjust the settings of F08.00 - F08.04
according to the nameplate of the motor. Start the motor parameter auto-tuning function and
properly set Group F10 parameters, so as to achieve excellent vector control efficiency.
F00.06
Max. output frequency of HD3N
50.00 - 400.00 [50.00Hz]
Defines the max. frequency that HD3N is allowed to output.
•
V/f: max. 400Hz; Vector control: max. 200Hz.
•
Please set F00.06 according to nameplate of motor and actual running conditions.
F00.07
Upper limit of running frequency setting channel
0 - 7 [0]
Defines the max. frequency that system is allowed to run, and use F00.07 to select setting channels to set
the upper limit frequency.
0: Digital setting. Set the upper limit frequency by F00.08.
1: Analogue input setting. Refer to Group F16.
2: Terminal pulse setting. Set by F16.17, and its max. pulse input frequency corresponds to F00.06 (max.
output frequency of HD3N).
3: AI1.
4: AI2.
7: Potentionmeter. Valid when LED keypad adopted only.
F00.08
Upper limit of running frequency
0.00 - F00.06 [50.00Hz]
F00.07 = 0, the upper limit frequency is set by F00.08.
F00.09
Lower limit of running frequency
0.00 - F00.08 [0.00Hz]
Use F00.09 to limit the actual output frequency. When Zero frequency threshold (F19.10)
<
setting
frequency
<
F00.09, HD3N will run at lower limit frequency.
•
Properly set F00.09 according to the nameplate of the motor and actual running conditions.
•
No limitation on the motor parameter auto-tuning function.
•
Besides the lower /upper limit frequency, the running frequency of inverter is also limited by
starting/stop DWELL frequency (F02.02, F02.14), zero frequency threshold (F19.10), starting frequency of
stop DC brake (F02.16) and skip frequency (F05.17 - F05.19).
6