Section V. Parameter Function Table
103
Display codes as below
:
HV610C series offers two groups of personalized parameter display mode
:
user customization
function mode, user change parameter mode.
In user customization parameter mode, sign u is added to the user customization function code as
default.
In user change parameter mode, sign c is added to the user customization function code as
default. E.g
:
F1.00 is displayed as cF1.00 .
FP.04
Function codes modification
attribute
Can be modified
0
0
☆
Can not be modified
1
This function is used to prevent misoperation of the function parameters.
FP.04=0
:
All the function codes can be modified.
FP.04=1
:
All the function codes can only be viewed, but not modified.
5.18 Torque control group
:
A0.00-A0.08
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
A0.00
Speed/ torque control mode
selection
Speed control
0
0
★
Torque control
1
A0.00 is used to select inverter control mode
:
speed control or torque control.
Multi-function digit DI terminal of HV610C is equipped with two functions relating torque control
:
Torque control banned(Function29), speed control/torque control switching (function 46). The two terminals
should be matched with A0.00 to realize switching between speed control and torque control.
A0.00 set the control mode when speed/torque control switching terminal invalid. If the speed/torque
control switching terminal is valid, control mode is equivalent to the inversion of A0.00 value.
When function 29 is valid, speed control mode is fixed for the inverter .
A0.01
Torque setup source selection
in torque control mode
Digital setup(A0.03)
0
0
★
AI1
1
AI2
2
AI3
3
PULSE
4
Communication setup
5
MIN(AI1,AI2)
6
MAX(AI1,AI2)
7
A0.03
Torque digital setup in torque
control mode
-200.0%~200.0%
150%
☆
A0.01 is used to select torque set source. There are totally 8 kinds of torque set mode.
Torque set is a relative value, which 100% corresponding to inverter rated torque. Set range
:
200.0%~200.0%.Maximum torque is 2 times that of inverter rated torque
When the torque is set by selection 1~7, 100% of communication ,analog input, pulse input
corresponding to A0.03.
A0.05
Torque control forward
maximum frequency
0.00Hz~Maximum frequency(F0.10)
50.00Hz
☆