Section V. Parameter Function Table
72
5.10 Auxiliary function
:
F8.00-F8.53
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
F8.00
Jog running frequency
0.00Hz~maximum frequency
2.00Hz
☆
F8.01
Jog acceleration time
0.0s~6500.0s
20.0s
☆
F8.02
Jog deceleration time
0.0s~6500.0s
20.0s
☆
It defines the reference frequency and acc. / dec. time of the inverter at the time of jogging.
The jog process is started and stopped according to direct startup mode(F6.00=0) and decelerate to
stop mode (F6.10=0).
F8.03
Acceleration time 2
0.0s~6500.0s
10.0s
☆
F8.04
Deceleration time 2
0.0s~6500.0s
10.0s
☆
F8.05
Acceleration time 3
0.0s~6500.0s
10.0s
☆
F8.06
Deceleration time 3
0.0s~6500.0s
10.0s
☆
F8.07
Acceleration time 4
0.0s~6500.0s
10.0s
☆
F8.08
Deceleration time 4
0.0s~6500.0s
10.0s
☆
HV610C offers 4 groups of speed-up/speed-down time,F0.17/F0.18 and 3 groups above.
F8.03 to F8.08 parameters have the same definition with F0.17 and F0.18.You can switch to choose
the 4 groups through different combination of DI multi-function digital input terminal.For specific using
method,please refer to function code F4.01~F4.05 for details.
F8.09
Hopping frequency 1
0.00Hz~maximum frequency
0.00Hz
☆
F8.10
Hopping frequency 2
0.00Hz~maximum frequency
0.00Hz
☆
F8.11
Hopping frequency amplitude
0.00Hz~maximum frequency
0.00Hz
☆
Hopping frequency 1
Hopping frequency 2
Output frequency
Hz
Hopping frequency amplitude
t
Hopping frequency amplitude
Hopping frequency amplitude
Hopping frequency amplitude
Fig.5-14 Skip frequency schematic diagram
When set frequency is within the range of hopping frequency,the actual running frequency will run
close to the set frequency of hopping frequency.Inverter can avoid load mechanical resonance by setting
hopping frequency.
HV610C can set 2 hopping frequency points,if both of them are set to 0,then the hopping frequency
function is canceled.Hopping frequency and hopping frequency amplitude schematic is shown in Fig5-14.
F8.12
Dead zone time of FWD&REV
0.00s~3000.0s
0.0s
☆
It refers to the transit time at the 0Hz output point when the inverter switches between forward rotation
and reverse rotation. As shown in figure 5-15.