Section V. Parameter Function Table
112
make the inverter work normally.
If the inverter long time continuous staying in rapid current-limiting state, it may occur overheating
fault, which is not allowed during operation. Fault alarm of long time rapid current-limiting is 40= Err40 ,
which refers to inverter overload and necessary stop.
A5.05
Current detection
compensation
0~100
5
☆
It is used to set inverter current detection compensation. Excessive setting may lead to decrease of
control performance.Generally do not need to be modified.
A5.06
Under-voltage point setup
60.0%~140.0%
100.0%
☆
A5.06 is used to set value of inverter under-voltage fault 9= E.LU. Different voltage level of 100.0%
corresponds to different voltage point,respectively
:
Single phase 220V or three-phase 220V
:
220V
Three-phase 380V
:
350V
Three phase 480V
:
450V
Three-phase 690V
:
650V
A5.07
SVC optimization mode
selection
No optimization
0
1
☆
Optimization mode 1
1
Optimization mode 2
2
0
:
No optimization
1
:
Optimization mode 1
It is used when there is high torque control linearity requirements.
2
:
Optimization mode 2
It is used when there is high speed stability requirement.
A5.08
Dead zone time adjustment
100%~200%
150%
☆
This parameter is set according to 1140V voltage level. By adjusting the value can improve the
voltage effective use rate. Users are not suggested to modify.
A5.09
Overvoltage point setup
200.0V~2500.0V
810.0V
☆
A5.09 is over-voltage point set through software, which is not related to hardware overvoltage
point.
5.22 AI curve setup
:
A6.00-A6.29
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
A6.00
AI curve 4 minimum input
-10.00V~A6.02
0.00V
☆
A6.01
AI curve 4 minimum input
corresponding setup
-100.0%~100.0%
0.0%
☆
A6.02
AI curve 4inflection point 1
input
A6.00~A6.04
3.00V
☆
A6.03
AI curve 4 inflection point 1
input corresponding setup
-100.0%~100.0%
30.0%
☆
A6.04
AI curve 4 inflection point 2
input
A6.02~A6.06
6.00V
☆
A6.05
AI curve 4 inflection point 2
input corresponding setup
-100.0%~100.0%
60.0%
☆
A6.06
AI curve 4 maximum input
A6.06~10.00V
10.00V
☆