Section V. Parameter Function Table
64
F5.06
FMP output function
selection(pulse output
terminal)
0-16
0
☆
F5.07
AO1 output function selection 0-16
0
☆
F5.08
AO2 output function selection 0-16
1
☆
FMP terminal output pulse frequency range
:
0.01kHz~F5.09 (FMP maximum frequency output), F5.09
could vary from 0.01kHz to 100.00kHz.
AO1, AO2 output ranges from 0V to 10V, or 0mA to 20mA.
The corresponding value range is shown in the table below
:
Setup
value
Function
Range
0
Running frequency
0~maximum output frequency
1
Setup frequency
0~maximum output frequency
2
Output current
0~200% of the rated current of the motor
3
Output torque
0~200% of the rated torque of the motor
4
Output power
0~200% of the rated power of the motor
5
Output voltage
0~120% of the rated voltage of the inverter
6
PULSE pulse input
0.01kHz~100.00kHz
7
AI1
0V~10V
8
AI2
0V~10V(Or 0~20mA)
9
AI3
0V~10V
10
Length
0~Maximum length
11
Counting value
0~Maximum counting value
12
Communication setup
0.0%~100.0%
13
Motor Speed
0~maximum output frequency corresponding speed
14
Output current
0.0A~1000.0A
15
Output voltage
0.0V~1000.0V
16
Output torque
-200%~200%of the rated torque of the motor
F5.09
FMP maximum output
frequency
0.01kHz~100.00kHz
50.00kHz
☆
When the multifunctional terminal output function selects FMP pulse output, it can set the maximum
frequency value of output pulse.