Section V. Parameter Function Table
69
The process of DC brake at stop is as shown in Figure below.
Fig.5-13 DC brake schematic diagram
F6.15
Brake utilization ratio
0%~100%
100%
☆
It is only valid for the inverter with built-in brake unit.
It is used to adjust the duty ratio of the brake unit.When the brake utilization ratio is high,then the duty
ratio of brake unit action is high,braking effect is strong.But there will be big fluctuation of inverter bus
voltage.
5.9 Keyboard and display
:
F7.00-F7.14
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
F7.01
JOG.K key function selection
JOG.K key invalid
0
0
★
Switching between operation panel
command channel&the remote command
channel (terminal command channel or
serial port command channel)
1
Switching between FWD&REV rotation
2
Forward JOG command
3
Reverse JOG command
4