Section V. Parameter Function Table
34
supplementary explanation of corresponding communication card for details.
Supplementary explanation for communication card is allotted with communication card.This manual
contains a brief description of communication card.
F0.03
Main frequency source X
selection
Digital setup(Preset frequency F0.08,
UP/DOWN can be modified, power off
without memory)
0
4
★
Digital setup(Preset frequency F0.08,
UP/DOWN can be modified, power off
with memory)
1
AI1
2
AI2
3
AI3
4
Pulse setup(X5)
5
MS command
6
Simple PLC
7
PID setup
8
Communicaton setup
9
This parameter is used to select the main reference frequency input channel. Totally 10 main reference
frequency channels
:
0
:
Digital setup(power off without memory)
Initial value of set frequency equals to F0.08 “preset frequency”.User can change inverter set
frequency value through keyboard
∧
key and
∨
key ( or multi-function input terminal UP,DOWN).
Inverter power on after powered off, frequency set value restored to F0.08 “Preset frequency”.
1
:
Digital setup(power off with memory)
Initial value of set frequency equals to F0.08 “preset frequency”. User can change inverter set
frequency value through keyboard
∧
key and
∨
key ( or multi-function input terminal UP,DOWN).
Inverter power on after powered off, frequency set value restored to the value that equals to setupof
last power off time. Correction is memorized through keyboard
∧
key and
∨
key or terminal UP,DOWN.
What needs to be reminded is, F0.23 is “Digital setup frequency memory selection”. F0.23 is used to
select correction whether to be memorized or cleared and is relevant to stop, irrelevant to power off
memory, please pay attention during operation.
2
:
AI1
3
:
AI2
4
:
AI3
The frequency is determined by the input terminal of the analog quantity. The HV610C control board
provides 3 analog input terminals (AI1, AI2, AI3). Among them, AI1 is 0V
~
10V voltage input, AI2 can be
0V
~
10V voltage input, or 4mA
~
20mA current input, which is selected by the J8 jumper on the control
board, AI3 is -10V
~
10V voltage input. 1. The input voltage value of AI2, AI3 and the corresponding
relationship with the target frequency can be freely selected by the user.
This series of inverters provide 5 sets of corresponding relationship curves, of which 3 sets of curves
are linear relationships (2-point corresponding relationships), and the user can set them through the F4
group function code. The 2 sets of curves are arbitrary curves with 4 points corresponding to the
relationship (factory parameters). The function code F4-33 is used to set the AI1~AI3 three-way analog
input, respectively select which one of the 5 groups of curves.
5
:
Pulse setup(X5)
Pulse setup is set through terminal pulse. Signal standard
:
voltage range 9V~30V, frequency range
0kHz~100kHz. Set pulse can be only input through multi-function input terminal X5.
Содержание HV610C Series
Страница 1: ...HV610C Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 25: ...Section II Installation Wiring 12 2 3 2 Typical wiring of HV610C in Crane applications ...
Страница 29: ...Section II Installation Wiring 16 Control board terminal layout ...
Страница 167: ......