Section V. Parameter Function Table
80
below 40
℃
F8.48=1
:
Cooling fan is always running after power-on.
F8.49
Wake up frequency
Sleep frequency(F8.51) ~maximum frequency
(F0.10)
0.00Hz
☆
F8.50
Wake up delay time
0.0s~6500.0s
0.0s
☆
F8.51
Sleep frequency
0.00Hz~wake-up frequency(F8.49)
0.00Hz
☆
F8.52
Sleep delay time
0.0s~6500.0s
0.0s
☆
This group of function codes are used to realize sleep and wake up function.
During operation
:
when set frequency is less than or equals to sleep frequency(F8.51), inverter would
step into sleep state and stop after sleep delay time(F8.52).
If inverter is in sleep state and current running command is valid, when set frequency is no less than
F8.49 wake-up frequency, inverter will start to run after F8.50 wake-up delay time.
Generally, please set wake-up frequency no less than sleep frequency. Sleep function and wake-up
function are valid when both wake-up frequency and sleep frequency are set to 0.00 Hz.
When enabling sleep function(frequency source
:
PID) , PID calculation selection in sleep state is
influenced by function code FA.28 (FA.28=1).
F8.53
The running time arrival
0.0Min~6500.0Min
0.0Min
☆
When the running time reached the F8.53 set value, inverter multi-function DO output “Then running
time arrival” ON signal.
5.11 Overload and protection
:
F9.00-F9.70
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
F9.00
Motor over load protection
selection
Invalid
0
1
☆
Valid
1
F9.01
Motor overload protection
gain
0.20~10.00
1.00
☆
F9.00=0
:
Without motor overload protection function. It is recommended to install a thermal relay
between the motor and the inverter.
F9.00=1
:
The inverter has overload protection function for the motor according to motor overload
protection inverse time limit curve.
Motor overload protection inverse time limit curve
:
220%×(F9.01)× motor rated current,it will report
motor overload fault after it lasts for one minute. When the operating current of the motor reaches the
current of 150%×(F9.01)times the rated current of the motor, it will report motor overload after it lasts 60
minutes.
Users can set value of F9.01 according to the motor actual overload ability.If the parameter is set too
big, it may cause danger of motor overheating damage without inverter fault report.
F9.02
Motor overload pre-alarm
coefficient
50%~100%
80%
☆
This function is used before motor overload fault by giving pre-alarm signal through multi-function
terminal DO.This pre-alarm coefficient is used to determine the warning timing before motor overload
protection. The higher the value,the shorter the warning timing will be.
When the inverter output current is accumulated more than the product of inverse time limit curve with
F9.02,multi-function terminal DO output “Motor overload pre-alarm”ON signal.
Содержание HV610C Series
Страница 1: ...HV610C Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 25: ...Section II Installation Wiring 12 2 3 2 Typical wiring of HV610C in Crane applications ...
Страница 29: ...Section II Installation Wiring 16 Control board terminal layout ...
Страница 167: ......
Страница 175: ......