Section V. Parameter Function Table
70
It is used to set the functions of multifunctional JOG.K key.
0
:
Invalid function
1
:
Operation panel command channel and remote command channel
It can perform switching between the current command source and keyboard control(local
operation).The function key is invalid when current command source is keyboard control.
2
:
Switching between forward and reverse rotation
Switching the rotary direction of the motor via the JOG.K key on the keyboard is only enabled when
the command source is “operation panel command”.
3
:
Forward jog
It can perform forward jog (FJOG) operation via the JOG.K key on the keyboard.
4
:
Reverse jog
It can perform reverse jog (RJOG) operation via the JOG.K key on the keyboard.
F7.02
STOP/RESET function
The stop function of STOP/RES key is
valid only in the keyboard control mode.
0
1
☆
The stop function of STOP/RES key is
valid in any control mode.
1
F7.03
LED running display
parameter1
0000~FFFF
1F
☆
7
6
5
4
3
2
1
0
Running frequency 1(Hz)
Setting frequency (Hz)
Bus voltage(V)
Output voltage(V)
Output current(A)
Output power(kW)
Output torque(%)
DI input status(V)
15 14 13 12 11 10
9
8
D0 output status
Count value
Length value
Load speed display
PID setting
AI1(V)
AI2(V)
AI3(V)
If the above parameters need to be displayed during the operation, users can set their corresponding
positions to 1 and then convert this binary number into Hexadecimall number and set it to F7.03.
F7.04
LED running display
parameter 2
0000~FFFF
0
☆
7
6
5
4
3
2
1
0
PID feedback
Surplus running time
PLC stage
Input pulse frequency (kHz)
Running frequency 2(Hz)
AI1 voltage before correction(V)
AI2 voltage before correction(V)
AI3 voltage before correction(V)
15
14 13 12
11 10
9
8
Linear speed
Communication setting
Encoder feedback speed
Present power-on time(Hour)
Present running time(Min)
Input pulse frequency(Hz)
Main frequency X display
Auxiliary frequency Y display
If the above parameters need to be displayed during the operation, users can set their corresponding
positions to 1 and then convert this binary number into Hexadecimal number and set it to F7.04.
Running display parameter is used to set paratermers which can be seen under inverter running state.
32 state parameters can be checked at most,you could choose the needed state parameter through
F7.03
、
F7.04 binary digit,display sequence starts from F7.03 lowest digit order.