Section V. Parameter Function Table
77
Running frequency
t
Random frequency arrival
Random frequency arrival
detection signal or relay
ON
ON
OFF
OFF
OFF
Frequency detection range
Frequency detection range
Fig.5-20 Random frequency arrival detection schematic diagram
When inverter output frequency is within the positive & negative detection range of random frequency
arrival detection value , multi-funtion terminal DO output ON signal.
F8.34
Zero-current detection level
0.0%~300.0%(Motor rated current)
5.0%
☆
F8.35
Zero-current detection delay
time
0.00s~600.00s
0.10s
☆
When inverter output current is less than or equals to zero-current detection level, and the lasting
time exceeds zero-current detection delay time,inverter multi-function terminal DO output DO signal.
Fig.5-21 is schematic diagram of zero-current detection.
Fig.5-21 Zero-current detection schematic diagram
F8.36
Output current overlimit value
0.0%(No detection)
0.1%~300.0%(Motor rated current)
200.0%
☆
F8.37
Output current overlimit
0.00s~600.00s
0.00s
☆