Section V. Parameter Function Table
35
Relationship between X5 input pulse frequency and corresponding settings is set through F4.28~F4.31. It
is linear relationship(2-point correspondence). Pulse input 100.0% refers to the percentage of F0.10 .
6
:
MS command
MS command running mode is set through different combination mode of digital input DI terminal.
There are 4 MS command terminals with 16 status of HV610C series. FC group function codes correspond
to 16 “MS command”. “MS command” is percentage relativing to F0.10 ( maximum frequency).
When digital input terminal DI is used as MS command terminal, user should set through F4 group.For
specifications please refer to F4 group.
7
:
Simple PLC
When frequency source is set to 7, running frequency source can be switched to any frequency
command during 1~16.
User can set frequency command retention time and acceleration/deceleration time respectively.For
specifications please refer to FC group .
8
:
PID
Running frequency is the output of PID control process. Generally used for field process closed-loop
control.
When PID is chosen, user should set relevant parameters of FA group “PID function”.
9
:
Communication setup
Means that the main frequency source is given by the host computer through communication
F0.04
Auxiliary frequency source
Y selection
Digital setup(preset frequency F0.08,
UP/DOWN adjustable, power off without
memory)
0
0
★
Digital setup(preset frequency F0.08,
UP/DOWN adjustable, power off with
memory)
1
AI1
2
AI2
3
AI3
4
PULSE setup (Dl5)
5
MS command
6
Simple PLC
7
PID setup
8
Communication setup
9
When the auxiliary frequency source is used as independent frequency reference channel (i.e.
frequency source switching from X to Y), it is used in the same way as the relative specifications of F0.03.
When the auxiliary frequency source is used as overlap reference (i.e. frequency source selection
switching from X plus Y or X to X plus Y), it has special points as follows
:
1. When the auxiliary frequency source is digital reference, the preset frequency (F0.08) is
nonsensical, and it needs to adjust the main reference frequency through the keys “
∧
”and “
∨
” of the
keyboard (or UP andDOWN of multifunctional input terminals).
2. When the auxiliary frequency source is analog input reference (AI1
、
AI2
、
AI3) or pulse input
reference, 100% of input setup is relative to the auxiliary frequency source range,and can be set through
F0.05 and F0.06.
3. When the frequency source is pulse input reference, it is similar to the analog value.
Prompt
:
There is difference between the auxiliary frequency source Y selection and the main
frequency source X setup value. That is to say, F0.03 and F0.04 cannot use the same frequency reference
channel.