Section V. Parameter Function Table
54
Schedule 3 Motor terminal selection description
:
Terminal2 Terminal1
Acc./dec. selection
Corresponding
parameter
OFF
OFF
Motor 1
F1
、
F2 group
OFF
ON
Motor 2
A2 group
F4.10
DI filter time
0.000s~1.000s
0.010s
☆
If the digital input terminal malfunction because it is vulnerable to interference , users could increase
the parameter value to enhance the interference immunity. However, this operation may cause reduced
sensitivity of the DI terminal.
Two-wires mode 1
0
Two-wires mode 2
1
Three-wires mode1
2
Three-wires mode2
3
This parameter defines 4 different modes of controlling the forward and reverse rotations of the inverter via
the external terminal.
NOTE:
:
In order to explain
,
The following arbitrary selection X1
~
X10 multifunctional input terminal X1
、
X2
、
X3 three terminals as external terminals
,
That is, by setting the value of F4.00
~
F4.02 to select X1
、
X2
、
X3 three terminal functions
。
Detailed function definition is F4.00
~
F4.09 setting range
0
:
Two-line mode 1
:
This mode is the most commonly used forward/reverse rotation control mode. The forward/reverse
rotation of the motor is decided by the X1, X2 terminal commands. The descriptions on the terminal running
command are as shown as below
:
Terminal
Set value
Description
X1
1
Forward(FWD)
X2
2
Reverse(REV)
Among them ,X1
、
X2 are X1~X10 muti-fuction input terminal, level valid.
0 invalid
,
1 valid
K1
K2
Command
0
0
Stop
0
1
Reverse(REV)
1
0
Forward(FWD)
1
1
Stop
Fig. 5-6 Two-line control mode 1
K2
K1
X1(FWD)
X2 (REV)
COM
HV610C