Section V. Parameter Function Table
109
A2.04
Rated frequency
0.01Hz~maximum frequency
-
★
A2.05
Rated Speed
1rpm~65535rpm
-
★
A2.06
Asynchronous motor stator
resistance
0.001Ω~65.535Ω(Inverter power <=55kW)
0.0001Ω~6.5535Ω(Inverter power >55kW)
-
★
A2.07
Asynchronous motor rotor
resistance
0.001Ω~65.535Ω(Inverter power <=55kW)
0.0001Ω~6.5535Ω(Inverter power >55kW)
-
★
A2.08
Asynchronous motor leakage
inductance
0.01mH~655.35mH(Inverter power <=55kW)
0.001mH~65.535mH(Inverter power >55kW)
-
★
A2.09
Asynchronous motor mutual
inductance
0.1mH~6553.5mH(Inverter power <=55kW)
0.01mH~655.35mH(Inverter power >55kW)
-
★
A2.10
Asynchronous motor no load
current
0.01A~A2.03(Inverter power <=55kW)
0.1A~A2.03(Inverter power >55kW)
-
★
A2.27
Encoder pulses number
1~65535
2500
★
A2.28
Encoder type
ABZ incremental encoder
0
0
★
UVW incremental encoder
1
Rotary transformer
2
Sine/cosine encoder
3
UVW encoder
4
A2.29
Speed feedback PG selection
Local PG
0
0
★
Expansion PG
1
PULSE pulse input(X5)
2
A2.30
ABZ incremental encoder AB
phase
Forward
0
0
★
Reserve
1
A2.31
Encoder installation angle
0.0°~359.9°
0
0
★
A2.32
UVW phase sequence
Forward
0
0
★
Reverse
1
A2.33
UVW encoder offset angle
0.0°~359.9°
0.00
★
A2.34
Rotary transformer pole pairs 1~65535
1
★
A2.36
PG dropped inspection time
No action
0.0s
0.0s
★
0.1s~10.0s
0.1s
A2.37
Tuning selection
No operation
0
0
★
Asynchronous static tuning
1
Asynchronous complete tuning
2
Synchronous static tuning
11
Synchronous complete tuning
12
A2.38 Speed loop proportional gain 1 1~100
30
☆