Section VI. Fault Diagnosis & Solutions
119
Fault name
External equipment fault
Panel display
Fault No.15= Err15
Fault investigation
1
、
Input external fault signal through DI
2
、
Input external fault signal through IO
Fault counter
measures
1
、
Reset operation
Fault name
Communication fault
Panel display
Fault No.16= Err16
Fault investigation
1
、
Abnornal communication cable
2
、
Wrongly set communication expansion card F0.28
3
、
Wrongly set communication parameter FD group
4
、
Position machine operation anomalies
Fault counter
measures
1
、
Check the communication cable
2
、
Set communication expansion card type correctly
3
、
Set communication parameter correctly
4
、
Check position machine cable
Fault name
Contactor fault
Panel display
Fault No.17= Err17
Fault investigation
1
、
Input phase lack
2
、
Drive board , contactor anomalies
Fault counter
measures
1
、
Eliminate external loop faults
2
、
Replace driver, power- supply board or contactor
Fault name
Current inspection fault
Panel display
Fault No.18= Err18
Fault investigation
1
、
Drive board anomalies
2
、
Hall devices anomalies
Fault counter
measures
1
、
Replace drive board
2
、
Replace hall devices
Fault name
Motor tuning fault
Panel display
Fault No.19= Err19
Fault investigation
1
、
Parameter identification process overtime
2
、
Wrongly set motor parameters
Fault counter
measures
1
、
Check wire between inverter and motor
2
、
Set motor parameters correctly according to the nameplate
Fault name
Encoder /PG card fault
Panel display
Fault No.20= Err20
Fault investigation
1
、
Encoder anomalies
2
、
PG card anomalies
3
、
Encoder type mismatch
4
、
Encoder connections fault
Содержание HV610C Series
Страница 1: ...HV610C Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 25: ...Section II Installation Wiring 12 2 3 2 Typical wiring of HV610C in Crane applications ...
Страница 29: ...Section II Installation Wiring 16 Control board terminal layout ...
Страница 167: ......
Страница 175: ......