Section IV. Keyboard Operation
25
05). Please input the parameters of the lower surface according to the actual
parameters of the motor (according to the current motor selection)
If it is an asynchronous motor, then F1-37 (tuning selection, for motor 2, it should
be FB-37 function code) please select 2 (asynchronous motor fully tuned), press
enter to confirm, at this point, the keyboard shows STUDY, as shown in the
following figure:
Then press the run key on the panel, the frequency inverter will drive the motor to
accelerate and decelerate, rotate forward and backward, the operation indicator light will
illuminate, and the operation duration will be recognized for about 2 minutes. When the above
display information disappears, the normal parameter display state will be returned, indicating
that the tuning is completed. After the complete tuning, the frequency inverter will automatically
calculate the following parameters of the motor:
F1 - 06: Asynchronous motor stator resistance
F1 - 07: Asynchronous motor rotor resistance
F1 - 08: Induction motor leakage inductance
F1 - 09: Induction motor mutual inductance resistance
F1 - 10: Asynchronous motor no-load current
If the motor cannot be completely disconnected from the load, F1- 29 (motor 2 is FB - 29)
please select 1 (asynchronous motor is still tuned), and then press the run key on the panel to
start the motor parameter identification operation.