Section V. Parameter Function Table
85
F9.41
First fault output terminal
The latest fault digital input terminal status, order as
below
:
BIT4
BIT3
BIT2
BIT1
BIT0
FMP
REL1
REL2
DO1
DO2
When output terminal status is ON, it’s corresponding
binary digit is 1. OFF corresponds to 0. All DO status
are converted to decimal display.
●
F9.42
First fault inverter state
Reserved
●
F9.43
First fault power-on time
The latest fault power-on time
●
F9.44
First fault running time
The latest fault running time
●
F9.47
Fault protection action
selection 1
1bit
Motor overload(Fault No.11= Err11)
00000
☆
Free stop
0
Stop according to stop mode
1
Keep on running
2
10bit
Input phase lack(Fault No 12=Err12)
Free stop
0
Stop according to stop mode
1
100
bit
Input phase lack(Fault No 13=Err13)
Free stop
0
Stop according to stop mode
1
1000
bit
External fault(Fault No.15=Err15)
Free stop
0
Stop according to stop mode
1
10000
bit
Abnormal communication(Fault
No.16=Err16)
Free stop
0
Stop according to stop mode
1
F9.48
Fault protection action
selection 2
1bit
Encoder fault (Fault No.20=Err20)
00000
☆
Free stop
0
Switch to VF, stop according to stop
mode
1
Switch to VF, keep on running
2
10bit
Abnormal communication(Fault
No.21=Err21)
Free stop
0
Stop according to stop mode
1