Section V. Parameter Function Table
71
F7.05
LED stop display parameter
0000~FFFF
33
☆
7
6
5
4
3
2
1
0
DI input status
Setting frequency(Hz)
Bus voltage(V)
DO output status
AI1 (V)
AI2 (V)
AI3 (V)
Counter
15 14 13
12 11 10
9
8
Length value
Reserved
Reserved
Reserved
PLC stage
Load speed
PID setting
Input pulse frequency(Hz)
If the above parameters need to be displayed at the time of stop, it can set their corresponding
positions to 1 and then convert this binary number into Hexadecimal number and set it to F7.05.
F7.06
Load speed coefficient
0.0001~6.5000
1.0000
☆
When display of the load speed is necessary, F7.06 is used to adjust the corresponding relationship
between inverter frequency output and load speed. For details please refer to F7.12.
F7.07
Inverter module radiator
temperature
0.0
℃
~100.0
℃
12
℃
●
It is used to display IGBT temperature.
Different model’s inverter module is set with different IGBT over temperature protection value.
F7.08
Product ID
0
℃
●
Display inverter product ID
F7.09
Accumulative running time
0h~65535h
0h
●
It is used to display the accumulated running time of the inverter. When the accumulated running time
reaches F8.17 setup running time, the multifunctional digital output terminal(12) will output ON signal.
F7.11
Software version No.
Control board software version No.
-
●
F7.12
Load speed display decimal
digits
No decimal place
0
1
☆
One decimal place
1
Two decimal places
2
Three decimal places
3
Decimal point position
:
It is used to set the number of decimal places of the load speed.
For example, if the Load speed display coefficient F7.06 is 2.000,load speed display decimal digits is
2(Two decimal places),when inverter running frequency is 40.00Hz,the load speed will be
:
40.00*2.000=80.00(2 decimal digit display)
If the inverter is in stopped state, then load speed displays as corresponding set frequency speed.Take
set frequency of 50.00Hz as an example,the stop state load speed is
:
50.00*2.000=100.00(Two decimal
places)
F7.13
Accumulative power-on time
0h~65535h
-
●
It displays accumulative power-on time since leaving the factory.
When it reaches the set power-on time (F8.17) , multi-function digital output (24) ON signal.
F7.14
Accumulative power
consumption
0~65535
-
●
It displays the inverter accumulative power consumption.