Section V. Parameter Function Table
114
Analog input AI1~AI3 of HV610C are all provided with hopping function for set value.
Hopping frequency refers to fixing of analog corresponding setup to the value of hopping point
when analog corresponding setting varies within jump point upper/lower limit.
E.g
:
Voltage of analog input AI1 is in 5.00V fluctuation, which range is 4.90V~5.10V. Minimum input
0.00V corresponding to 0.0%, while maximum input 10.00V corresponding to 100.%.The corresponding
setting of AI1 fluctuates between 49.0%~51.0%.
Set A5.16 to 50.0% and A5.17 to 1.0%, after hopping function processing, AI1 is fixed as 50.0%. In
this way, AI1 is converted into a stable input, and fluctuation is eliminated.
5.23 User programmable card parameters
:
A7.00-A7.09 Reserved
5.24 Point to point communication
:
A8.00-8.11
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
A8.00
Master slave control
function selection
Invalid
0
0
☆
Valid
1
A8.01
Master slave selection
Master
0
0
☆
slave
1
A8.02
Master slave information
exchange
0 bit
Do not follow the Master
command
0
011
☆
follow the Master command
1
10 bit
Do
not
send
fault
information
0
send fault information
1
100 bit
Do not warning when slave
off line
0
warning when slave off line
1
A8.03
Message frame selection
Master slave control frame
0
0
☆
Droop control frame
1
A8.04
Receive data zero
offsettorque
-100.00%
~
100.00%
0.00
★
A8.05
Receive data gain torque
-10.00
~
100.0
1.00
★
A8.06
Communication interrupt
detection time
0.0s
~
10.0s
1.0s
☆
A8.07
Communication Master
data transmission cycle
0.001s
~
10.000s
0.001
☆