158
inverter immediately outputs
the command to close the
brake.
A9-03
Run up hold time
Factory default
:
0.3s
Range
:
0~20.0s
This time is from start brake
to full brake, During this
period, the inverter keep the
frequency output of A9-02
A9-04
Run
down
release
frequency
Factory default
:
0.6hz
Range
:
0~20.00hz
Output frequency before the
brake is fully opened.
A9-05
Run down release time
Factory default
:
0.2s
Range
:
0~20.0s
During the time from the start
opening to the full opening of
the mechanical brake,
the
inverter keep the frequency
output of A9-04.
A9-06
Run down hold frequency
Factory default
:
3.00hz
Range
:
0~20.00hz
After the running command is
canceled, when the output
frequency during the stop is
lower than the set value, the
inverter immediately outputs
the command to close the
brake.
A9-07
Run down hold time
Factory default
:
0.5s
Range
:
0~20.0s
This time is from start brake
to full brake, During this
period, the inverter keep the
frequency output of A9-06.
A9-29
Elevator enable
0:Invalid
1:Valid
F5-02
Relay function
03
:
Braking for translation
46
:
Braking for lifting