Section V. Parameter Function Table
78
detection delay time
Output current
Output current overlimit
detection signal
t
t
P8.36
ON
P8.37
Fig.5-22 Output current overlimit detection schematic diagram
When inverter output current is larger than output current overlimit value (F8.36) ,and lasting time
exceeds the software overlimit detection delay time ,inverter multi-function terminal DO output ON signal,
fig.5-22 is schematic diagram of output current overlimit detection.
F8.38
Random current arrival 1
0.0%~300.0%(Motor rated current)
100.0%
☆
F8.39 Random current arrival range1
0.0%~300.0%(Motor rated current)
0.0%
☆
F8.40 Random current arrival 2
0.0%~300.0%(Motor rated current)
100.0%
☆
F8.41 Random current arrival range2
0.0%~300.0%(Motor rated current)
0.0%
☆
When inverter output current is within the positive & negative detection range of random arrival current
value , multi-funtion terminal DO output ON signal.
HV610C offers two groups of random current arrival range detection parameters ,as shown in fig. 5-23.