5 Control system
Standard operation sequence
SMGB0091 rev.2 - 11/2015
85
5
Pressing
RUN/STOP
switch
Stop of inverter
Stop of MC
I.U: Indoor unit
R.U: RASC unit
Power to CMC: OFF
Indoor fan motor MIF: OFF
Temperature
on the top of
compressor
After
3 minute
20 seconds
> 80 ºC
< 75 ºC
Power to CH: ON
Power to CH: OFF
Power to Y52C: OFF
Stop of MOF
Lower than 50 ºC
Higher than 50 ºC
RUN/STOP lamp: OFF
HEAT, set fan speed & set temperature indication:
continuously ON
STOP
Power to
indoor unit:
OFF
Power to
RASC unit:
OFF
LCD indication: OFF
Power to PCB in indoor unit: OFF
Power to CH: OFF
Power to PCB in RASC unit: OFF
Slow fan speed
IU
discharge air
temp.
Operation
at slow speed
Lower than 40 ºC
After 2 minute
Higher than 40 ºC
Shorter than 2 min.
Reset of timer for defrosting
from 1
Pressing
AUTO-LOUVER switch
Stop of
AUTO-LOUVER
Start of
AUTO-LOUVER
Alternatively
Only for air panel
or Indoor Unit
with Auto-Louver